Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 63

Advertising
background image

63

Defaults
Group

Relay Range Description

Single Synch- Multi- Constant Speed

18

Outputs

Pump ronous Control Slave Control

1804 Relay RO2

Selects the AV status to be

Run-

Run-

Run-

Start

Run-

Output

indicated through relay output 2 ning

ning

ning

Slave

ning

(RO2). The relay energizes when

the status meets the setting.

Relay warnings are reset

automatically, faults must be

manually reset.

Not Sel

The output is not used

Run (Default)

The output indicates the drive

is running.

VFD Fault

The drive has faulted

Low Water

The secondary protection

warning or fault function has

been activated. DI4 is low for

the protection delay setting

(2404). Closed = normal,

Open = Secondary Protect fault

function

is

active.

Pump Protect The pump protection warning or

fault function has been activated.

Start Slave

Used in multipump macro to

start slave pump only.

Stand by

Drive is in sleep mode due to

no system demand.

1805 RO2 ON Delay

0…3600 s

Defines the operation delay for

0

0

0

0

0

relay output RO2.

1806 RO2 OFF Delay 0…3600 s

Defines the release delay for

0

0

0

0

0

relay output RO2.

1807 Relay RO3

Selects the AV status to be

Not

Not

Not

Not

Not

Output

indicated through relay output 3 Used

Used

Used

Used

Used

(RO3). The relay energizes when

the status meets the setting.

Relay warnings are reset

automatically, faults must be

manually reset.

Not Sel (default) The output is not used

Run

The output indicates the drive is

running.

Ready

The output indicates that power

is supplied to the drive and it is

awaiting a start command.

VFD Fault

The drive has faulted

PARAMETER LISTINGS