Technical data, Fuse sizing/ratings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 134

Advertising
background image

134

Fuse Sizing/Ratings

380…480 Volt Drives
The following table provides Aquavar CPC rating information and recommended fuse sizing
for the input short circuit protection. Branch circuit protection must be provided by the end
user, contractor or distributor. Sized according to local or applicable NEC codes.

CENTRIPRO AQUAVAR CPC

NEMA 1

Full

NORMAL

Frame

Input

Fuse Type

3

Voltage Phase

Base

Load

DUTY

Size

Current

JJN

Model

Amps

HORSEPOWER

Amps

CPC40061 6.9

3

R1

7.0

10

CPC40081 8.8

5

R1

9.0

15

CPC40121 11.9

7.5

R1

12.1

15

CPC40151

15.4 10 R2

15.7 20

CPC40231 23

15

R2

23.5

30

CPC40311 31

20

R3

31.6

40

CPC40381 38

25

R3

38.8

45

CPC40451 45

30

R3

44.9

60

CPC40591 59

40

R4

60.2

70

CPC40721 72

50

R4

73.4

90

CPC40771 77

60

R4

78.5

90

460

3 CPC40971 97

75

R4

98.0

125

CPC41251 125

100

R5

126.5

150

CPC41571 157

125

R6

160.1

200

CPC41801 180

150

R6

183.6

225

CPC42451 245

200

R7

250.0

300

CPC43161 316

250

R7

322.3

400

CPC43681 368

300

R8

375.4

450

CPC44141 414

350

R8

422.3

500

CPC44861 486

400

R8

495.8

600

CPC45261 526

450

R8

536.5

800

CPC46021 602

500

R8

614.0

800

CPC46451 645

550

R8

658.0

800

(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type

JJN and JJS are shown in the Aquavar CPC tables. Other manufaturers are acceptable if they meet fuse
requirements.