Installation – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 31

Advertising
background image

31

You can wire the digital input terminals in either a PNP or NPN configuration.

PNP Connection (Source)

NPN Connection (Sink)

Communications

Terminals 28…32 are for RS485 or modbus communications. Use shielded cables. For lengths
of cable beyond 100 feet, use screen connections.

Do not directly ground the RS485 network at any point. Ground all devices on the network
using their corresponding earthing terminals.

As always, the grounding wires should not form any closed loops, and all the devices should
be earthed to a common ground.

Terminate the RS485 network using 120 Ω resistors at both ends of the network. Use the DIP

switch to connect or disconnect the termination resistors. See following diagram and table.

1

For functional descriptions, see “Standard Serial Communication” addendum.

INSTALLATION

(Frames R1-R6)

X1

10 +24V

11 GND

12 DCOM

13 DI1

14 DI2

15 DI3

16 DI4

17 DI5

18 DI6

X1

10 +24V

11 GND

12 DCOM

13 DI1

14 DI2

15 DI3

16 DI4

17 DI5

18 DI6

Terminated

Station

Station

Station

Terminated

Station

X1 Identification
28 Screen
29 B
30 A
31 AGND
32 Screen

SCR

B

A

GND

B

A

GND

SCR

28 SCR

29 B

30 A

31 AGND

32 SCR

ON ON

ON ON

RS485 Multidrop Application

Other Modbus Devices

Hardware Description

1

RS485 Interface

J2 J5

J2 J5

off position on position

Bus Termination

RS485
Multipump
Connections