Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 55

Advertising
background image

55

Defaults
Group

Locks/ Range Description

Single Synch- Multi- Constant Speed

10

Passwords

Pump ronous Control Slave Control

1004 Parameter Save Save

Used for manually saving

Done Done

Done

Done

Done

(continued)

parameters that have been

altered through the fieldbus

connection.

1005 New Pass Code 0…300000

Sets new pass code for

0

0

0

0

0

parameter lock. Returns to 0

after saving.

1006 Set Point Lock

Disables set point changes

Off

Off

Off

Off

Off

from the keypad.

Off (Default) Local control allowed.

On

Local control allowed.

Group

Start-Up

Range Description

Single Synch- Multi- Constant Speed

11

Data

Pump ronous Control Slave Control

1101 Language

Selects the display language

English English English

English

English

English (AM)

American English.

(Default)

Español

Spanish (full translation)

Francais

French (full translation)

1102 Application

Selects the application macro

Macro

Single Pump

One AV regulating to a set point

(Default)

Synchronous

Lag pumps start as needed and

all pumps regulate to the set

point at the same speed. Note:

it is recommended that all

pumps be identical.

Multicontrol

Lag pumps start as needed. The

last lag pump to start regulates

to the set point; the remaining

pumps operate at an enable

sequence speed (2203).

Constant Slave The master unit starts up to

three fixed speed slave units

when needed. See RO1, RO2

and RO3 settings (parameters

1801, 1804 and 1807).

Speed Control AV follows a speed reference

only. Pump protect fault

function is inactive.

1103 Application

No

Resets parameters to default

Restore

Yes

settings.

PARAMETER LISTINGS