Cable Sizing/Ratings

380…480 Volt Drives
The following table provides Aquavar CPC rating information and
recommended wire sizing for the input and output cables.

CENTRIPRO AQUAVAR CPC

NEMA 1

Full

NORMAL

Frame

Output

Input

Voltage Phase

Base

Load

DUTY

Size

2

Cable Size

Cable Size

Model

Amps

HORSEPOWER

Min. AWG

1

Min. AWG

1

CPC40061 6.9

3

R1

14

14

CPC40081 8.8

5

R1

14

14

CPC40121 11.9

7.5

R1

14

14

CPC40151 15.4

10

R2

12

12

CPC40231 23

15

R2

12

12

CPC40311 31

20

R3

10

8

CPC40381 38

25

R3

8

8

CPC40451 45

30

R3

8

6

CPC40591 59

40

R4

6

4

CPC40721 72

50

R4

4

3

CPC40771 77

60

R4

4

3

460

3 CPC40971 97

75

R4

3

1

CPC41251 125

100

R5

1

2/0

CPC41571 157

125

R6

2/0

3/0

CPC41801 180

150

R6

3/0

4/0

CPC42451 245

200

R7 350MCM 350MCM

CPC43161

316

250

R7

2 X 250MCM 2 X 250MCM

CPC43681

368

300

R8

2 X 300MCM 2 X 300MCM

CPC44141

414

350

R8

2 X 400MCM 2 X 400MCM

CPC44861

486

400

R8

2 X 500MCM 2 X 500MCM

CPC45261

526

450

R8

2 X 350MCM 2 X 350MCM

CPC46021

602

500

R8

2 X 500MCM 2 X 500MCM

CPC46451

645

550

R8

2 X 500MCM 2 X 500MCM

(1) Recommended AWG Size based on NEC table 310.16, 40º C ambient, 90º C, UL type copper wire. For other

wire sizes or types, consult local, state or NEC codes.

(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult

technical section (CABLE TERMINALS) for maximum wire diameter and torque values.

TECHNICAL DATA