MultiPump – Slave Pump Control

Programming Steps
Default settings for each relay are set for NOT USED. Therefore,
the operator will have to access the programming, and go to
GROUP 18 “RELAY OUTPUTS” and set each relay to START
SLAVE. (SEE BELOW FOR DETAILED PROGRAMMING

STEPS.) Each relay is labeled (R01, R02, R03) and can be
programmed to respond based on a drop in system pressure
and delay time in seconds. Therefore, you can control the relay
when the system pressure starts to drop, and you allow a certain time delay in seconds to
respond. When the demand stops, each LAG pump will stop after a time delay, and operation
will return solely to the Aquavar controlled pump.

1. Access the main menu on the keypad. Press the MENU key

once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
“parameters” option, then press the “ENTER” key.

2. Once the parameters option has been chosen, the

parameter groups will be displayed. Each group will be
numbered (see parameter groups list on page 50 for
detailed information). Use the arrow keys to highlight the
parameter group 10, “LOCKS/PASSWORDS”, then press the
SEL key.

3. Use the arrow keys to highlight group 1002 “PASSCODE”,

then press the EDIT key. Enter your factory password number
(Default is 66). Press the save key.

4. Use up arrow to group 1001 “PARAMETER LOCK”, then

press the EDIT key. Next, use the up arrow to select
“OPEN“, then press the SAVE key. This group should
appear as “OPEN”, if it does not you have entered the pass
code incorrectly, or it has changed. Contact your local
CentriPro representative for the master code. Once your
group 1001 is showing “OPEN”, you can access the entire
pump and drive parameters in the Aquavar.

DIR

MENU

REM

27.0%

40.2 PSI

sp

0.0 PSI

ac

0.0 HZ

EXIT

ENTER

REM

MAIN MENU

1

PARAMETERS

WIZARDS

CHANGED PAR

EXIT

SEL

REM

PAR GROUPS

10

01 VFD SIGNALS

02 PUMP SIGNALS

03 FB ACTUAL SIGNALS

10 LOCKS/PASSWORDS

11 START-UP DATA

EXIT

EDIT

REM

PARAMETERS

1001 PARAMETER LOCK

1002 PASS CODE

0

1003 LOCAL LOCK

1004 PARAM SAVE

EXIT

EDIT

REM

PARAMETERS

1001 PARAMETER LOCK

OPEN

1002 PASS CODE

1003 LOCAL LOCK

1004 PARAM SAVE

PROGRAMMING