MultiPump – Slave Pump Control

10. After saving your motor horsepower, press the EXIT key. Use

the down arrow until you highlight the group 15 “XDUCER
VARIABLES”, then press EDIT.

11. Press the down arrow until parameter 1502 TRANSDUCER

MAX is highlighted, then press EDIT. Default pressure
transducer setting is 300 psi. Adjust this based on your
maximum rating for a new transducer. NOTE: CentriPro
provides a 0 -300 psi transducer as standard. Select the
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.

12. Use the down arrow to highlight 1503 “TRANSDUCER MIN”

0.0, then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer value, press
SAVE to store.

13. Use the down arrow to highlight 1506 “SENSOR MIN”,

then press EDIT. Use the up arrow until the “TUNE” value is
displayed, press the SAVE key. This provides the transducer
a tuned value of 0 (ZERO) psi. NOTE: Make sure that your

transducer is wired to the Aquavar but free from any

pressure in the system. The transducer must be exposed
to 0 psi when this step is performed. Press the SAVE key to
tune your transducer.

EXIT

SEL

REM

15 XDUCER VARIABLES

16 REFERENCE SELECT

18 RELAY OUTPUTS

19 ANALOG OUTPUTS

21 REGULATE

PAR GROUPS

15

EXIT

EDIT

REM

PARAMETERS

1501 TRANSDUCER UNIT

1502 TRANSDUCER MAX

300.0

1503 TRANSDUCER MIN

1504 SENSOR

EXIT

EDIT

REM

PARAMETERS

1501 TRANSDUCER UNIT

1502 TRANSDUCER MAX

1503 TRANSDUCER MIN

0.0

1504 SENSOR

PROGRAMMING

EXIT

EDIT

REM

PARAMETERS

1504 SENSOR

1505 K-DP FLOW METER

1506 SENSOR MIN

TUNE

CANCEL

SAVE

REM

PAR EDIT

1506 SENSOR MIN

4 mA

CANCEL

SAVE

REM

PAR EDIT

1506 SENSOR MIN

TUNED VALUE