Installation – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 28
![background image](/manuals/310443/28/background.png)
28
Wiring IP 54 / UL Type 12 Enclosure with Conduit
1. Remove and discard the clamping plate.
2. Remove and discard the cable seals where
conduit will be installed. (The cable seals are
cone-shaped, rubber seals on the bottom of the
drive.)
3. For each conduit run, install water tight conduit
connectors (not supplied).
4. Route the power wiring through the conduit.
5. Route the motor wiring through the conduit.
6. Strip the wires.
7. Connect the power, motor and ground wires to
the drive terminals. See “Power Connections” on
page 29.
8. Route the control wiring through the conduit.
9. Strip the control cable sheathing and twist the
copper screen into a pigtail.
10. Connect the ground screen pigtail for digital and
analog I/O cables X1-1.
11. Strip and connect the individual control wires to
the drive terminals. See “Control Connections” on
pages 29 and 30.
12. Install the conduit/gland box cover (1 screw).
13. Install and wire transducer as stated in previous
steps on pages 27 and 28.
INSTALLATION
(Frames R1-R6)