Faults/alarms, Correcting faults – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 116

Advertising
background image

116

Correcting Faults

The recommended corrective action for faults is:

• Use the “Fault Listing” table below to find and address the root cause of the problem.
• Reset the drive. See “Fault Resetting” on page 119.

* Drive not ready fault. Check supply voltage / DC Bus = 1.35 x input voltage.
* Comm fault drive not responding. Internal communication lost.

• Cycle Power • Remove and reinstall panel • Replace panel

Fault Listing
Fault Fault Name

Description and Recommended Corrective Action

Code In Panel

1 OVERCURRENT

Output current is excessive. Check for and correct:

• Excessive motor load, pump overload.

• Insufficient acceleration time (parameters 1301 Ramp 1 and 1302 Ramp 2).

• Faulty motor, motor cables or connections.

2 DC OVERVOLT

Intermediate circuit DC voltage is excessive. Check for and correct:

• Static or transient overvoltages in the input power supply.

• Insufficient deceleration time (parameters 1302 Ramp 2, increase to at least

8 seconds).

3 DEV OVERTEMP

Drive heatsink is overheated. Temperature is at or above 115º C (239º F).

Check for and correct:

• Fan failure

• Excessive ambient temperature

• Obstructions in the air flow

• Excessive motor load

• Dirt or dust coating

• Ambient temperature

on the heat sink

• Altitude

4 SHORT CIRC

Fault current. Check for and correct:

• A short-circuit in the motor cable(s) or motor

• Supply disturbances

5 OVERLOAD

Inverter overload condition. The drive output current exceeds the ratings given

in “Ratings” on pages 131-134 of this manual.

6 DC UNDERVOLT

Intermediate circuit DC voltage is not sufficient. Check for and correct:

• Missing phase in the input power supply

• Blown fuse/check input wiring

• Undervoltage on mains

7

AI

1 LOSS

Analog input 1 loss. Analog input value is less than

AI

1

MIN

(1604).

Check for and correct:

• Source and connection for analog input.

• Parameter settings for

AI

1

MIN

(1604).

8

AI

2 LOSS

Analog input 2 loss. Analog input value is less than

SENSOR MIN

(1506).

Check for and correct:

• Source and connection for analog input.

• Parameter settings for

SENSOR MIN

(1506) and (1503)

TRANSDUCER MIN

.

9 MOT OVERTEMP

Motor is too hot, based on either the drive’s estimate or on temperature

feedback device.

• Check for overloaded motor.

• Adjust the parameters used for the estimate (1104…1109).

• Check the temperature sensors and Group 11 parameters.

• Check motor wiring and connections. Possible MOTOR phase loss.