Single Pump Programming (Pressure transducer)

16. Optional Step: To lock out access to the control panel (keypad), refer to page 109. This

will prevent unauthorized users from changing programming.

NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual, page 116. When troubleshooting an Aquavar system, always break down into the
following components:

1. Aquavar programming — check default settings recommended for single pump, multi-

pump, slave pump etc.

2. Electrical supply/ motor/ wiring/grounding — check your supply voltage, motor

wiring, transducer wiring, and grounding.

3. Mechanical/Pump/ Rotation — check your pump rotation, rubbing or other mechanical

problems. Pump “run out”.

4. Hydraulic System/ Piping — check to ensure proper suction and discharge piping

layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.

5. Environment — protect from high temperatures, direct sun, freezing temperatures, high

altitude, dust, vibration, lack of air flow.