Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 77
![background image](/manuals/310443/77/background.png)
77
Single Pump Programming (Pressure transducer)
16. Optional Step: To lock out access to the control panel (keypad), refer to page 109. This
will prevent unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual, page 116. When troubleshooting an Aquavar system, always break down into the
following components:
1. Aquavar programming — check default settings recommended for single pump, multi-
pump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding — check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation — check your pump rotation, rubbing or other mechanical
problems. Pump “run out”.
4. Hydraulic System/ Piping — check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment — protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
PROGRAMMING