RAMP HYSTERESIS
Ramp hysteresis is the point at which the Aquavar controller changes over from the fast
ramp to the slow ramp. Default values of Ramp Hysteresis are in % of the regulation window.
The values for RAMP HYSTERESIS are automatically selected based upon the control mode
selection made during programming.

EXAMPLE: Using the same example above, the Regulation Window was 8 psig. An 80% ramp hysteresis would
be 3.2 PSIG. Note from the graph, this is 1.6 PSIG on the upper half of the regulation window, and 1.6 PSIG on
the lower half of the regulation window.

Parameter

Name

Value/Range

Note(s)

13.05

RAMP

0-100%

Pressure = 80%

HYSTERESIS

Flow [Direct] = 5%

As the figure shows, Aquavar attempts to keep the actual process reading within the Setpoint

Hysteresis Window using the slow acceleration and deceleration ramp rates. When the

process reading exceeds this window, it will compensate using the fast acceleration or

deceleration ramp rates.

Adjusting Ramp Rates
Ramp 1 - Fast Acceleration
: This ramp is the fast run up time used when the pump first
starts and is trying to reach the setpoint. A setting too fast may overshoot the set-point, while
a setting too slow may cause the drive to respond too slowly to set point changes. NOTE:

FOR AQUAVAR UNITS ABOVE 10 HP, SET RAMP 1 AND RAMP 2 TO AT LEAST 8 – 10

SECONDS.
Parameter

Name

Value/Range

Note(s)

13.01

RAMP 1

0-1800s

Pressure default = 5 seconds

FAST ACCEL

Level, Temperature default = 20 seconds

FEATURES

Set Point

R1

R3

R4

Set P

oint Scale

[e.g

. Pr

essu

re

- PSIG,

Flow - GPM,

etc.]

Time

R1 - Ramp 1, Fast Acceleration
R2 - Ramp 2, Fast Deceleration
R3 - Ramp 3, Slow Acceleration
R4 - Ramp 4, Slow Deceleration

Set P

oint

Hyster

esis

Window

R4

R3

Window Set

ting

% of

Set P

oint

Hysteresis -%

Hysteresis -%

R1