Analog Outputs
The Aquavar CPC has two 4-20 mA analog outputs as standard. These outputs may be
configured by the user to output from a selection of nine actual pump signals. Parameter
group 19 is used to configure these outputs. Analog Outputs are found on X1 Terminal Block,
# 2 and # 5 pins. Reference the terminal block diagram on pages 24-31 for detailed wiring
connections.

Parameter

Name

Value/Range

Note(s)

19.01

AO 1

Not SEL (default)

CONNECTS an ANALOG SIGNAL TO

Content Sel

MOTOR FREQUENCY

THE ANALOG OUTPUT. RANGE IS

MOTOR CURRENT

0-20mA input.

MOTOR POWER

MOTOR PROC VAR

MOTOR ENERGY

SAVNGS

19.06

AO 2

Not SEL (default)

CONNECTS an ANALOG SIGNAL TO

Content Sel

MOTOR FREQUENCY

THE ANALOG OUTPUT. RANGE IS

MOTOR CURRENT

0 – 20mA input.

MOTOR POWER

THIS IS THE DEFAULT PRESSURE

MOTOR PROC VAR

TRANSDUCER INPUT. 4 – 20Ma.

MOTOR ENERGY

SAVNGS

21.01

REGULATION NORMAL (DEFAULT)

SELECTS THE TYPE OF AQUAVAR

MODE

INVERSE

CONTROL AS THE ANALOG SIGNAL

RISES OR FALLS. SET TO INVERSE FOR

DECREASED MOTOR SPEED BASED ON

SUCTION LEVEL TRANSDUCER.

26.03

SAVINGS

0-65535

If ENERGY SAVNG is selected as an

SCALE

Default – 10,000

output, this parameter must be set to

scale the signal. 4 mA = $0.00 and

20 mA equals this amount. For example

20 mA = $10,000.

Auto Restart
The Aquavar drive can be configured to start automatically following a power failure.
Changing the value to ON will enable auto-restart. Selecting OFF disables the auto-restart.
AUTO RESTART is also used with ERROR RESET for automatic restarts following a shutdown
due to a pump fault. AUTO RESTART will also restart the pump once a secondary protection
fault is reset.

Parameter

Name

Value/Range

Note(s)

12.02

AUTO

OFF

When this is set to “ON “, the Aquavar

RESTART

ON (DEFAULT)

will automatically re-start after a power

failure or fault reset.

25.04

AR OVER-

ENABLE

Allows the drive to restart after a motor

CURRENT

overcurrent error.

25.05

AR OVER-

ENABLE

Allows the drive to restart after an

VOLTAGE

INPUT OVERVOLTAGE error.

25.06

AR UNDER-

ENABLE

Allows the drive to restart after an

VOLTAGE

INPUT UNDERVOLTAGE error.

25.07

AR AI <

ENABLE

Allows the drive to restart after a

MIN

transducer or analog signal loss.