Defaults
Group

Regulate Range

Description

Single Synch- Multi- Constant Speed

21

Pump ronous Control Slave Control

2102 Press Incr Speed 0…60 Hz

Sets the speed for which

20 20 20 20 20

additional pressure is added to

compensate for system frictional

losses at increased flow. Used for

single pump and backup modes

only. Default = 20 Hz.

2103 Press Incr

0….10000

The pressure increase in selected

0 0 0 0 0

units point which is added to the

set point pressure to compensate

for frictional losses at the pressure

increase speed. Used for single

pump and backup modes only.

Note the full set point pressure

increase (%) is achieved at

maximum speed (1401).

Group Multipump

Range Description

Single Synch- Multi- Constant Speed

22

Control

Pump ronous Control Slave Control

2201 Value Decrease 0…1000

Defines how much the actual

5

5

5

5

5

can drop before the next lag

pump is started. Used for

multicontrol, synchronous

control and slave modes only.

2202 Value Increase

0….1000

Defines the increase in set point

5

5

5

5

5

when a lag pump starts. This

value is cumulative with each

lag pump that turns on. Used

for multicontrol, synchronous

control and slave modes only.

The default setting for 2202 is

equal to the value set in 2201.

2203 Enable Sequence 0… 60 Hz

Defines the speed the drive

59

59

59

59

59

must be at before multipump

operation is allowed.. Applies to

synchronous, multicontrol and

slave modes only. Default =

98% of 1401 Maximum Speed.

2204 Switch Lead Lag 1…100 h

Defines the time the lead unit

48

48

48

48

48

will run before a new unit is

deemed the lead unit. Note if

set to 1001 (Not SEL) the

switching function is disabled

(including switching during a

fault). Default setting is 48 hrs.

PARAMETER LISTINGS