MultiPump – Constant Pressure Control

Wiring/Connection RS485
Each Aquavar unit must be connected via terminals

29, 30 and 31. Using a three wire shielded cable

between each Aquavar terminal. Suggested wire

specifications would be 3 or 4 wire, 22AWG, one

pair shielded, TYPE CM or CL3, 75 degree C(UL).

Remember to keep the color coded wires the same

to each terminal connection, and inspect for loose or

bad connections.

When using all the same Aquavar CPC units, you must

provide a BUS TERMINATION for the last drives in the

multi-pump system. The RS485 has two yellow DIP

SWITCHES that must be in the ON position when that Aquavar CPC unit is the last or first in

the system. Therefore, if you have 4 pumps in multi-pump configuration, Aquavar address 1

and Aquavar address 4 would have their DIP SWITCHES in the ON position (see diagram). If

you have a DUPLEX system, then Aquavar address 1 and Aquavar address 2 would have the

switches in the ON position.

Always follow your local codes or National codes and have a certified electrician perform the

necessary wiring.

NOTE: Fieldbus cannot be used with RS485 multipump (Modbus, Devicenet,

Profibus). Single pump only!