Window Setting (Reg Window)
Aquavar controls the set-point within a defined window. This window, called the Regulation
Window [Parameter 13.06 REG WINDOW] is automatically set based upon the operating
modes and instrument type selected during programming. Values may be adjusted in
parameter 13.06.

EXAMPLE: if the Aquavar unit was in pressure control with the set point at 100 psig, the regulation window
would be factory preset at 8% of the set point. This would result in an 8 PSIG window; 4 PSIG above the set point
and 4 PSIG below the set point.

Parameter

Name

Value/Range

Note(s)

13.06

REG

0-100%

Constant Pressure = 8%

WINDOW

Flow [Direct] = 30%

Suggested settings are above in the notes. Sometimes the REGULATION WINDOW will have to be adjusted to
smooth out the system pressure. Default setting is 8%.

NOTE: If the system pressure drops below or goes above the hysteresis limits (DASHED
lines), then the Aquavar control software will adjust the speed with the fast ramps. This
would occur if you have a rapid demand of water in your system. Normally it takes a few
seconds to level off.

FEATURES

Set Point

R1

R2

R3

R4

Set P

oint Scale

[e.g.

P

ressur

e - PSIG,

Flow - GPM,

etc.]

Time

R1 - Ramp 1, Fast Acceleration
R2 - Ramp 2, Fast Deceleration
R3 - Ramp 3, Slow Acceleration
R4 - Ramp 4, Slow Deceleration

10s

50s

Set P

oint

Hyster

esis

Window