Technical data, Fuse sizing/ratings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 133

Advertising
background image

133

Fuse Sizing/Ratings

208…240 Volt Drives
Branch circuit protection must be provided by the end user, electrical contractor or distribu-
tor, sized per local, state or local National Electrical Codes. Recommendations for fused
circuit protection are in the following tables.

CENTRIPRO AQUAVAR CPC

NEMA 1

Full

NORMAL

Frame

Input

Fuse Type

3

Voltage Phase

Base

Load

DUTY

Size

Current

JJN

Model

Amps

HORSEPOWER

Amps

CPC20171 8.5

2

R1

17.3

20

CPC20241 12

3

R2

24.5

30

CPC20311 15.5

5

R2

31.6

40

CPC20461 23

7.5

R3

46.9

60

CPC20591

29.5 10 R3

60.2 70

230

1 CPC20881 44.0

15

R4

89.8

110

CPC21141 57.0

20

R4

116.3

150

CPC21431 71.5

25

R6

145.9

175

CPC21781 89.0

30

R6

181.6

225

CPC22211 110.5

40

R6

225.4

300

CPC22481 124.0

50

R6

252.9

300

CPC20121 11.8

3

R1

12.0

15

CPC20171 16.7

5

R1

17.0

25

CPC20241 24.2

7.5

R2

24.7

30

CPC20311

30.8 10 R2

31.4 40

CPC20461

46.2 15 R3

47.1 60

CPC20591

59.4 20 R3

60.6 70

230

3

CPC20751

74.8 25 R4

76.3 90

CPC20881 88.0

30

R4

89.8

110

CPC21141 114.0

40

R4

116.3

150

CPC21431 143.0

50

R6

145.9

175

CPC21781 178.0

60

R6

181.6

225

CPC22211 221.0

75

R6

225.4

300

CPC22481

248.0 100 R6

252.9 300

(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type

JJN and JJS are shown in the Aquavar CPC tables. Other manufaturers are acceptable if they meet fuse
requirements.

* Bussmann is a registered trademark of Cooper Industries Inc.

TECHNICAL DATA

Advertising