Technical data, Control connection, Efficiency – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 137: Cooling

Advertising
background image

137

Control Connection

Control Connection Specifications

Analog Inputs

See table heading “Hardware Description” on page 29.

and Outputs
Digital Inputs

Digital input impedance 1.5 kΩ. Maximum voltage for digital

inputs is 30 V.

Maximum contact voltage: 30 V DC, 250 V AC

• Maximum contact current / power: 6 A, 30 V DC; 1500 VA, 250 V AC

• Maximum. continuous current: 2 A rms (cos ϕ = 1), 1 A rms

Relays

(cos ϕ = 0.4)

(Digital Outputs)

• Minimum load: 500 mW (12 V, 10 mA)

• Contact material: Silver-nickel (AgN)

• Isolation between relay digital outputs, test voltage:

2.5 kV rms, 1 minute

Cable Specifications

See “Control Cables” on page 17.

Efficiency

(Frames R1-R8)

Approximately 98% at nominal power level.

Cooling

(Frames R1-R6)

Cooling Specifications

Method

Internal fan, flow direction from bottom to top.

Free space around the unit:

Requirement

• 200 mm (8 in) above and below the unit.

• 25 mm (1 in) along each side of the unit.

TECHNICAL DATA