Parameters wizards changed par, Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 74

Advertising
background image

74

Single Pump Programming (Pressure transducer)

Programming Step(s)

1. Access the main menu on the keypad. Press the MENU key

once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
“parameters” option, then press the “ENTER” key .

2. Once the parameters option has been chosen, the

parameter groups will be displayed. Each group will be
numbered (see parameter groups list on page 50 for
detailed information). Use the arrow keys to highlight the
parameter group 10, “LOCKS/PASSWORDS, then press the
SEL key.

3. Use the arrow keys to highlight group 1002 “PASSCODE”,

then press the EDIT key. Enter your factory password
number (Default is 66). Press the save key.

4. Use up arrow to group 1001 “PARAMETER LOCK”, then

press the EDIT key. Next, use the up arrow to select “OPEN“,
then press the SAVE key. This group should appear as
“OPEN”, if it does not you have entered the pass code
incorrectly, or it has changed. Contact your local CentriPro
representative for the master code. Once your group 1001
is showing “OPEN”, you can access all of the pump and
drive parameters in the Aquavar.

5. After the SAVE key is pressed in the above group, press

the EXIT key, then the down arrow to highlight the group
11 “START UP DATA”, then Press the SEL key once. Using
the arrows, highlight 1102 “APPLIC MACRO”, then press
the EDIT key. Default is set for SINGLE PUMP. Change
this group whether your system is Single Pump, Multi-
Pump, Slave Pump etc. To exit press CANCEL, to save this
parameter, press the SAVE key once.

6. Use down arrow until group parameter 1104 “MOTOR

NOM VOLTAGE” is highlighted, then press EDIT. Use the
arrows to enter your motors nameplate voltage, then press
the SAVE key.

EXIT

EDIT

REM

PARAMETERS

1101 LANGUAGE

1102 APPLIC MACRO

SINGLE PUMP

1104 MOTOR NOM VOLT

1105 MOTOR NOM CURR

EXIT

SEL

REM

PAR GROUPS

10

01 VFD SIGNALS

02 PUMP SIGNALS

03 FB ACTUAL SIGNALS

10 LOCKS/PASSWORDS

11 START-UP DATA

EXIT

EDIT

REM

PARAMETERS

1001 PARAMETER LOCK

1002 PASS CODE

0

1003 LOCAL LOCK

1004 PARAM SAVE

EXIT

EDIT

REM

PARAMETERS

1001 PARAMETER LOCK

OPEN

1002 PASS CODE

1003 LOCAL LOCK

1004 PARAM SAVE

EXIT

ENTER

REM

MAIN MENU

1

PARAMETERS

WIZARDS

CHANGED PAR

PROGRAMMING

EXIT

EDIT

REM

PARAMETERS

1101 LANGUAGE

1102 APPLIC MACRO

1104 MOTOR NOM VOLT

230V

1105 MOTOR NOM CURR