Single Pump – Submersible Pump Constant Pressure

12. Next step will set the appropriate time delay in seconds at

the MINIMUM FREQUENCY. Use the down arrow until you
highlight parameter 1404 STP DELY MIN SPD, and then
press the EDIT key. Use the UP ARROW to select a time in
seconds. A suggested delay time is 5 seconds. When the
pump reaches the minimum frequency, it will have a delay
of 5 seconds before shutting down. Once entered, then
press the SAVE key.

13. From group 1404, press the down arrow until group 1502

TRANSDUCER MAX is highlighted, then press EDIT. Default
pressure transducer setting is 300 psi. Adjust this based on
your maximum rating for a new transducer. NOTE: CentriPro
provides a 0 -300 psi transducer as standard. Select the
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.

14. Use the down arrow to highlight 1503 “TRANSDUCER MIN”

0.0 , then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer valve, press
SAVE to store.

15. Use the down arrow to highlight 1506 “SENSOR MIN”,

then press EDIT. Use the up arrow until the “TUNE” value is
displayed, press the SAVE key. This provides the transducer
a tune value of 0 (ZERO) psi.

NOTE: Make sure that your transducer is wired to the
Aquavar but free from any pressure in the system. The
transducer must be exposed to 0 psi when this step is
performed. Press the SAVE key to tune your transducer.

EXIT

EDIT

REM

PARAMETERS

1401 MAXIMUM FREQ

1402 MINIMUM FREQ

1403 CONFIG SPEED MIN

1404 STP DELY MIN SPD

5 s

PROGRAMMING

EXIT

EDIT

REM

PARAMETERS

1504 SENSOR

1505 K-DP FLOW METER

1506 SENSOR MIN

4 mA

CANCEL

SAVE

REM

PAR EDIT

1506 SENSOR MIN

TUNED VALUE

EXIT

SEL

REM

15 XDUCER VARIABLES

16 REFERENCE SELECT

18 RELAY OUTPUTS

19 ANALOG OUTPUTS

21 REGULATE

PAR GROUPS

15

EXIT

EDIT

REM

PARAMETERS

1410 UNDERVOLT CTRL

1411 PRIMING DELAY

1501 TRANSDUCER UNIT

1502 TRANSDUCER MAX

300.0