Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 82

Advertising
background image

82

Single Pump – Submersible Pump Constant Pressure

6. Use down arrow until group parameter 1104 “MOTOR NOM

VOLTAGE” is highlighted, then press EDIT. Use the arrows to
enter your motors nameplate voltage, then press the SAVE
key.

7. Use the down arrow until group parameter 1105 “MOTOR

NOM CURRENT” is highlighted, then press EDIT. Using the
arrows, enter your motor’s maximum allowed amp draw at

full

speed, or Service Factor Amps. NOTE: Enter motor service
factor from nameplate or motor manual. Once you have
entered the amps, press the SAVE key.

8. Use down arrow until you highlight group parameter 1107

“MOTOR NOM RPM”, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3550
RPM. Press the SAVE key to store setting.

9. Use down arrow until you highlight group parameter 1108

“MOTOR NOM POW”, then press the EDIT key. Use arrows to
enter the motors Horsepower rating from nameplate, then
press the SAVE key.

10. Once you have saved parameter 1108, use the down

arrow until you highlight group parameter 1201 “START/
STOP”, then press EDIT. Default is “KEYPAD”. This parameter
determines how the operator will control the Aquavar; via
the keypad or via MODBUS communication. If no changes
are required, press the CANCEL key then EXIT and go to the
next step.

11. From group 12, press the down arrow until group 14 “SPD

LIM/STRT LVL” is highlighted, and then press SEL. Use down
arrows to highlight group 1402 “MINIMUM FREQ”, then
press EDIT. Using the arrow keys select the appropriate
minimum speed in HZ. Default is 10% of the parameter 1106
MOTOR NOM FREQ which is 6 HZ. For a submersible motor
or suction lift situation, this would be set to at least 30 HZ.
Depending upon the static water level, and pipe distance to the transducer, you may have
to increase this setting up to 40HZ. Once changed, press the SAVE key to store the setting.

EXIT

EDIT

REM

PARAMETERS

1101 LANGUAGE

1102 APPLIC MACRO

1104 MOTOR NOM VOLT

230V

1105 MOTOR NOM CURR

EXIT

EDIT

REM

PARAMETERS

1104 MOTOR NOM VOLT

1105 MOTOR NOM CURR

1106 MOTOR NOM FREQ

1107 MOTOR NOM RPM

3550 RPM

EXIT

EDIT

REM

PARAMETERS

1105 MOTOR NOM CURR

1106 MOTOR NOM FREQ

1107 MOTOR NOM RPM

1108 MOTOR NOM POW

1.0 HP

EXIT

EDIT

REM

PARAMETERS

1101 LANGUAGE

1102 APPLIC MACRO

1104 MOTOR NOM VOLT

1105 MOTOR NOM CURR

3.4A

PROGRAMMING

EXIT

EDIT

REM

PARAMETERS

1111 MOTOR ID RUN

1201 START/STOP KEYPAD

1202 AUTO RESTART

1203 TEST RUN

EXIT

EDIT

REM

PARAMETERS

1401 MAXIMUM FREQ

1402 MINIMUM FREQ

30.0 HZ

1403 CONFIG SPEED MIN

1404 STP DELY MIN SPD

Advertising