Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 57

Advertising
background image

57

Defaults
Group

Start/Stop Range

Description

Single Synch- Multi- Constant Speed

12

Pump ronous Control Slave Control

1203 Test Run

Automatic

If selected and the drive has not

(continued)

run for the test delay (1205) the

drive will start and run at 50%

of maximum speed (1401) for

20 seconds and shutdown.

Auto Restart 1202 must be on.

Manual

Once manual is selected the

Not Sel Not Sel Not Sel Not Sel Not Sel

drive will start and run at test

speed (1204) for 20 seconds

and shutdown. Once the

manual test is complete this

parameter will return to

“Not Sel”.

1204 Test Speed % (FL) 0...100%

Selects the speed the test runs

25% 25% 25% 25% 25%

at in manual test mode (1203).

1205 Test Run Delay

0...3600 Hr

Selects how long after the drive

1000 1000 1000 1000 1000

is idle before it will do a test run.

1206 Motor Jog

Jogs motor for 10 sec @ 60 RPM Disabled Disabled Disabled Disabled Disabled

to check for motor rotation.

1209 Manual

Disabled

Drive will run at constant speed

Override

(Default)

as set in Parameter 1210 when

enabled and contact DI5 is active.

1210 Override

0-60 Hz

Sets motor speed when manual

Freq

override is active.

Group

Ramps/

Range Description

Single Synch- Multi- Constant Speed

13

Windows

Pump ronous Control Slave Control

1301 Ramp 1 Fast Accel 0…1800 sec

Defines the fast acceleration time.

5

5

5

5

5

1302 Ramp 2 Fast Decel 0…1800 sec

Defines the fast deceleration time.

5

5

5

5

5

1303 Ramp 3 Slow Accel 0…1800 sec

Defines the slow acceleration time.

60

60

60

60

60

1304 Ramp 4 Slow Decel 0…1800 sec

Defines the slow deceleration time.

60

60

60

60

60

1305 Ramp Hysteresis

0…100 %

Per cent of window set aside

80

80

80

80

80

for hysteresis error.

1306 Reg Window

0…100 %

Window around the set point

which the control algorithm

8

8

8

8

8

operates.

Group

Spd Lim/

Range Description

Single Synch- Multi- Constant Speed

14

Strt Lvl

Pump ronous Control

Slave Control

1401 Maximum

Minimum

Defines the allowable maxi-

60

60

60

60

60

Frequency/Speed Frequency…

mum speed. Default setting

60 Hz

is parameter 1106 Motor Nom

Freq. (May want to show RPM

or HZ.)

PARAMETER LISTINGS