Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 52

Advertising
background image

52

Defaults
Group VFD Signals

Range

Description

Single Synch- Multi- Constant Speed

01

Pump ronous Control Slave Control

0101 Motor

0.0...500.0 Hz Calculated VFD output

Frequency

frequency, Hz

0102 Motor Current

0...2.0*I

2hd

Measured Motor Current, A

0103 Motor Power

-2...2*P

hd

Motor Power, kW

0104 DC Bus Voltage 0…2.5*V

dn

Measured intermediate circuit

voltage, V

0105 Motor Voltage

0…2.0*V

dn

Calculated motor voltage, V

0106 Drive Temp

0…150º C

VFD Temp, Deg C

0107 VFD On Time

0…9999h

Elapsed time counter; runs

when the drive is powered, Hrs

(since last reset). Re-settable by

parameter 2605.

0108 Run Time

0…9999h

Motor run time counter, Hrs

(since last reset). The counter

runs when the inverter

modulates. Re-settable by

parameter 2605.

0109 KWh Counter

0…9999kWh kWh counter, kWh (since last

reset). Re-settable by parameter

2605.

0110 DI6-1 Status

000000…

Status of digital inputs.

111111

Example: 0000001=DI1 is on,

DI2-DI6 off

0111 AI1

0…100 %

Value of analog input 1, %

0112 AI2 Trnsdcr Fdbk 0…100 %

Value of analog input 2, %

0113 RO3-1 Status

000…111

Status of relay outputs.

Example: 001=RO1 is energized,

RO2 & RO3 are de-energized.

0114 AO1[mA]

0…20 mA

Value of analog output 1, mA

0115 AO2[mA]

0…20 mA

Value of analog output 2, mA

0116 Last Fault

Fault Codes

Last fault code of the drive.

0117 Previous Fault 1 Fault Codes

Previous fault code of the drive.

0118 Previous Fault 2 Fault Codes

Oldest fault code of the drive.

0119 Fault Time 1

0120 Fault Time 2

0121 Speed at Flt

- RPM

Speed at the time of the latest

fault.

0122 Freq at Flt

- Hz

Frequency at the time of the

latest fault.

0123 Voltage at Flt

- V

DC bus voltage at the time of

the latest fault.

NOTE: Group 01 is read-only. Used for monitoring.

PARAMETER LISTINGS