Multi-pump level control, Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 86
![background image](/manuals/310443/86/background.png)
86
MULTI-PUMP LEVEL CONTROL
Submersible Transducer Setup
PARAMETER SETTINGS QUICK LIST
1002 — Pass Code = 66
1001 — Parameter Lock = OPEN
1102 — Application Macro = MULTIPUMP
1104 — Motor Nom. Volt.
1105 — Motor Nom. Current
1106 — Motor Nom. Freq.
1107 — Motor Nom. RPM
1108 — Motor Nom. Pow.
2101 — Regulation Mode = INVERSE
1501 — Transducer Unit = FT
2207 — Pump Address = 1, 2, 3 or 4
SYSTEM TUNING
Group 13 — Ramps allow for tuning of the system response. Ramps 1 and 2 provide control
of start and stop ramps and can be used to produce smooth operation throughout pumping
level. Ramps 3 and 4 work within the regulation window to provide a final adjustment of
system operation when needed (reference pages 112-114).
NOTE: Level control application performance is dependant on sump size, maximum flow
rate and pump selection. An oversized pump may produce on/off type system operation,
similar to a level switch. This condition might not be fully correctable with ramp control.
PROGRAMMING