Multi-pump level control, Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 86

Advertising
background image

86

MULTI-PUMP LEVEL CONTROL

Submersible Transducer Setup

PARAMETER SETTINGS QUICK LIST

1002 — Pass Code = 66

1001 — Parameter Lock = OPEN

1102 — Application Macro = MULTIPUMP

1104 — Motor Nom. Volt.

1105 — Motor Nom. Current

1106 — Motor Nom. Freq.

1107 — Motor Nom. RPM

1108 — Motor Nom. Pow.

2101 — Regulation Mode = INVERSE

1501 — Transducer Unit = FT

2207 — Pump Address = 1, 2, 3 or 4

SYSTEM TUNING

Group 13 — Ramps allow for tuning of the system response. Ramps 1 and 2 provide control
of start and stop ramps and can be used to produce smooth operation throughout pumping
level. Ramps 3 and 4 work within the regulation window to provide a final adjustment of
system operation when needed (reference pages 112-114).

NOTE: Level control application performance is dependant on sump size, maximum flow
rate and pump selection. An oversized pump may produce on/off type system operation,
similar to a level switch. This condition might not be fully correctable with ramp control.

PROGRAMMING

Advertising