Discharge Header

Flow Switch

Speed Signal

1

Parameter

Name

Value/Range

Note(s)

18.01

RELAY R0

NOT USED

Default for RO1

OUTPUT

18.04

RELAY R02

RUNNING

Default for RO2

OUTPUT

18.07

RELAY R03

READY

Default for RO3

OUTPUT

VFD FAULT

SECND PRTECT A

Secondary Protect A activation.

PUMP PROTECT

Pump protection activation.

START SLAVE

Used with multi-pump macro only.

STAND BY

NOTE: When using relay outputs to activate constant speed pumps in a multi-pump
application, the slave pumps 1, 2 and 3 should utilize relay outputs RO1, RO2, and RO3
accordingly (Slave 1 → RO1). Sequence logic is affected by these selections.

Restart Options
Parameter 14.05 — See MINIMUM SPEED OPTIONS

Low Water (Suction) Protection
The Aquavar provides protection from “dry-run” conditons in pressure, level, temperature and
speed control modes. This feature may also be used to provide inter-lock capabilities. In these
cases, additional system condition inputs (e.g. level switch, pressure switch, flow switch, etc…)
are used to alert Aquavar of conditions that require protection of the pump.

Once wired, parameter 24.05 LOW WATER must be set to WARNING or WARN AND
CONTROL. Digital Input 2 (DI 2), terminal # 14 on the X1 terminal board. If this contact is
OPEN, the response being:

1. WARN & CONTROL – In this response, Aquavar will issue a warning and then either shut

down or reduce speed depending on your settings. At this point the pump will behave
similar to the description in MINIMUM SPEED. Alarm & Control is the recommended
setting.