2. WARNING ONLY – In this response, Aquavar will simply issue an alarm/warning displayed

on the keypad screen, but continues to operate.

NOTE: The WARNING ONLY mode may result in damage to the pump if a low water
condition occurs. It is recommended to set this for WARN & CONTROL.

Keypad Failure
In the event of a keypad failure, Aquavar has been configured to fault and shut down the
controller. This functionality can be disabled, or configured to result in a drive fault.

Parameter

Name

Value/Range

Note(s)

24.01

KEYPAD

DISABLED (default)

Fault message - “PANEL LOSS”

FAILURE

FAULT

Set Points, Dual
The Aquavar can alternate between two fixed set points or one fixed point and a variable
set point. The alternating between set points may be accomplished using a digital switch or
through a Fieldbus command.

Parameter

Name

Value/Range

Note(s)

16.01

SP1/SP2

SETP 1 [Default]

This parameter defines the source that

SELECT

DI4

toggles the Aquavar unit between

FIELDBUS

Set Point 1 or Set Point 2.

• SET POINT 1 (Default) indicates that

only set point 1 is being used.

• DI4 is a digital input where “0”

(Open) selects Set Point 1 and “1”

(Closed) selects Set Point 2.

16.02

SET POINT 1

KEYPAD (Default)

This selects where the value for

SEL

AI 1

Set Point-1or 2 is coming from.

FIELDBUS

• KEYPAD - a number [e.g. 100] will

be manually entered via the keypad.

Selecting ANALOG INPUT will require

entry of parameters 16.03-16.04.

16.03

SET POINT 2

KEYPAD (Default)

This selects where the value for

SEL

ANALOG INPUT

Set Point-1or 2 is coming from.

FIELDBUS

• KEYPAD - a number [e.g. 100] will

be manually entered via the keypad.

Selecting ANALOG INPUT will require

entry of parameters 16.03-16.04.

22.08

SET POINT 2

OFF, 1…4

Must select source.

SOURCE

EXAMPLE for 16.02 and 16.03 – An irrigation system requires 110 psi for watering all zones, then
during the daytime normal water pressure is set for 60 psi.

FEATURES