117

Fault Fault Name

Description and Recommended Corrective Action

Code In Panel

10 PANEL LOSS

Panel communication is lost and either:

• Drive is in local control mode (the control panel displays LOC) or

• Drive is in remote control mode (REM) and is parameterized to accept start/

stop, direction or reference from the control panel.

To correct check:

• Communication lines and connections for control panel.

• Parameter 2401

KEYPAD FAILURE

.

• Parameters in Group 10: Command Inputs and Group 11:

Reference Select (if drive operation is REM).

11 ID RUN FAIL

The motor ID run was not completed successfully. Check for and correct:

• Motor connections, wiring.

12 MOTOR STALL

Motor or process stall. Motor is operating in the stall region.

Check for and correct:

• Excessive load

• Insufficient motor power

• Blocked pump

13 RESERVED

Not used

14 PUMP PROTECT

Pressure has fallen below value in Group 2403

15 LOW WATER

DI12 has been activated. Check for proper suction supply.

16 EARTH FAULT

The load on the input power system is out of balance.

• Check for/correct faults in the motor or motor cable.

• Verify that motor cable does not exceed maximum specified length.

17 UNDERLOAD

Motor load is lower than expected. Check for and correct:

• Disconnected load

• Drive oversized

18 THERM FAIL

Internal fault. The thermistor measuring the internal temperature of the drive is

open or shorted. Contact your local factory representative.

19 OPEX LINK

Internal fault. A communication-related problem has been detected on the

fiber optic link between the OITF and OINT boards. Contact your local factory

representative.

20 OPEX PWR

Internal fault. Low voltage condition detected on OINT power supply.

Contact your local factory representative.

21 CURR MEAS

Internal fault. Current measurement is out of range. Contact your local factory

representative.

• Replace drive

22 SUPPLY PHASE

Ripple voltage in the DC link is too high. Check for and correct:

• Missing mains phase

• Blown fuse

• Input wiring/connections

23 RESERVED

Not used

24 OVERSPEED

Motor speed is greater than 120% of the larger (in magnitude) of 1402

MINIMUM SPEED

or 1401

MAXIMUM SPEED

. Check for and correct:

• Parameter settings for 1401 and 1402

• Adequacy of motor braking torque

• Applicability of torque control

25 RESERVED

Not used

26 DRIVE ID

Internal fault. Configuration Block Drive ID is not valid.

Contact your local factory representative.

FAULTS/ALARMS