Technical data, Cable terminals – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 135

Advertising
background image

135

Cable Terminals

(Frames R1-R6)

Mains and motor cable maximum sizes (per phase) accepted at the cable
terminals and the tightening torques are listed below.

U1, V1, W1

Earthing PE

Control Wire

Frame

U2, V2, W2

“Ground”

Size Maximum Torque Maximum Torque Maximum Torque

Wire Size

Wire Size

Wire Size

mm

2

AWG Nm lb-ft mm

2

AWG Nm lb-ft mm

2

AWG Nm lb-ft

R1

6

8

1.4 1.0 4

10 1.4 1.0

R2 10

6

1.4

1.0

10

8

1.4

1.0

R3 25

3

1.8

1.3

16

6

1.8

1.3

R4

50 1/0 2.0 1.5 35

2 2.0 1.5 1.5 16 0.4 0.3

R5

70 2/0 15 11.1 70 2/0 15 11.1

R6 185 350 40 29.5 95 4/0 8 5.9

MCM

Cable Terminals

(Frames R7-R8)

Mains and motor cable maximum sizes (per phase) accepted at the cable terminals and the
tightening torques are listed below.

U1, V1, W1, U2, V2, W2

Earthing PE

Frame Number Cable Tightening Tightening

Size of holes Diameter Torque Torque

per

Screw Screw

phase

mm

in

Nm lb-ft Nm lb-ft

R7

2

58 2.28

M12 50…75 35…55

M8 15…22 10…16

R8

3

58 2.28

M12 50…75 35…55

M8 15…22 10…16

NOTE: Maximum AWG size for R7 Frame is (2) x 500MCM.

Maximum AWG size for R8 Frame is (3) x 500MCM.

TECHNICAL DATA

Advertising