Defaults
Group

Fault Range Description

Single Synch- Multi- Constant Speed

24

Functions

Pump ronous Control Slave Control

2403 Protection Limit 0…6553.5

This is the protection limit in PSI

0

0

0

0

0

for the process value at which

Pump Protect Ctrl (2402)

activates when pump is at max

speed for the protection delay.

2404 Protection Delay 0…200 s

This is the protection delay

0

0

0

0

0

period prior to activation of

Pump Protect Ctrl (2402).

Default setting is “0 sec”.

2405 Low Water

Loss of digital input 2 (DI2) for

Dis-

Dis-

Dis-

Dis-

Dis-

protection delay (2404).

abled abled

abled

abled

abled

Disabled

Protection is disabled.

(Default)

Warn

The AV generates a warning

only “Secondary Protect A”; no

other action is taken.

Warn and

Parameter 1202 Auto Restart

Control

must be set to “On” to

automatically restart once fault

has been reset.

2406 Error Reset

0…9999

Indicates number of fault resets.

0

0

0

0

0

Note parameter 1202 Auto

Restart must be set to “on”.

When set to “0” Error Reset is

disabled. Time between resets is

parameter 2407 Reset Delay.

Manual intervention is required

if fault is still active after set

number of resets has been

achieved. The drive reaction to

the fault will be according to

parameter 1405 Config Speed

Min setting. Reset is applicable

to parameters 2404 and 2405.

2407 Reset Delay

1…250 s

Defines the time that the AV will 60 s

60

60

60

60

wait after an alarm and control

condition before attempting an

error reset.

2408 Run Enable

DI1 has to be closed for drive to

be able to run.

Disable

Run Enable is not in use

Enable

DI1 is used for Run Enable

Function.

PARAMETER LISTINGS