Wizard Mode
When the drive is first powered up, the Start-Up Wizard guides you through the setup of a few
basic parameters. For example, at the first start, the drive automatically suggests entering the
first task, password.
The Start-Up Wizard is divided into tasks. You may activate the tasks one after the other, as the
Start-Up Wizard suggests, or independently. (You are not required to use the assistant, you
may use instead, the parameter mode to set the drive parameters.)
The order of the tasks presented by the Start-Up Wizard depends on your entries. The task list
in the following table (next page) is typical.

Start-Up Wizard

The start-up wizard is a tool that can be used to quickly program an Aquavar with the most
commonly used single / mult-pump parameters. The wizard will prompt the programmer to
enter the required parameters by automatically bringing them to the screen. To enable the
wizard following the steps below:

1. In the main screen select MENU. Then press enter.
2. Press the up / down arrow to select WIZARDS, then press SELECT.
3. Enter the values for the parameters as seen in the table below, and follow each entry by

pressing the SAVE key.

4. When complete, press the EXIT key until the main screen is displayed again.
5. Set the required system pressure using the up and down arrows, then start the pump

using the green START key.

Task Name

Description

10.02 Pass Code

Pass word setting to open the parameter lock.

10.01 Parameter Lock

Enables or disables the parameters from being changed.

11.01 Language

Selects the display language.

11.04 Motor Nom Voltage

Defines the motor nameplate voltage.

11.05 Motor Nom Current

Defines the motor nameplate current.

11.06 Motor Frequency

Defines the motor nameplate frequency.

11.08 Nominal Motor Power Defines the motor nominal power.

15.06 Sensor Min

Adjusts the transducer to a zero reference point.

Changed Parameters Mode
Use the Changed Parameters Mode to view (and edit) a listing of all parameters that have
been changed from default values.
Procedure:

1. Select CHANGED PAR in the Main Menu. The display lists all changed parameters.
2. Press ENTER.
3. Press UP/DOWN to select a changed parameter. As each parameter is highlighted, the

parameter value appears.

4. Press EDIT to edit the parameter value.

START-UP