Air Flow, 208…240 Volt Drives
The following table lists heat loss and air flow data for 208…240 Volt drives.

CENTRIPRO AQUAVAR CPC

NEMA 1

Full

NORMAL

Frame

Heat Loss Air

Voltage Phase

Base

Load

DUTY

Size Flow

Model

Amps

HORSEPOWER

Watts

BTU/HR CFM

CPC20171 8.5

2

R1 161 551 26

CPC20241 12

3

R2 227 776 52

CPC20311 15.5

5

R2 285 373 52

CPC20461 23

7.5

R3 420 1434 79

CPC20591 29.5

10

R3 536 1829 79

230

1 CPC20881 44.0

15

R4 786 2685 165

CPC21141 57.0

20

R4 1014 3463 165

CPC21431 71.5

25

R6 1268 4431 238

CPC21781 89.0

30

R6 1575 5379 238

CPC22211 110.5

40

R6 1952 6666 238

CPC22481 124.0

50

R6 2189 7474 238

CPC20121 11.8

3

R1 116 404 26

CPC20171 16.7

5

R1 161 551 26

CPC20241 24.2

7.5

R2 227 776 52

CPC20311 30.8

10

R2 285 373 52

CPC20461 46.2

15

R3 420 1434 79

CPC20591 59.4

20

R3 536 1829 79

230

3 CPC20751 74.8

25

R4 671 2290 165

CPC20881 88.0

30

R4 786 2685 165

CPC21141 114.0

40

R4 1014 3463 165

CPC21431 143.0

50

R6 1268 4431 238

CPC21781 178.0

60

R6 1575 5379 238

CPC22211 221.0

75

R6 1952 6666 238

CPC22481 248.0

100

R6 2189 7474 238

TECHNICAL DATA