Technical data, Input power (mains) connection, Motor connection – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 136

Advertising
background image

136

Input Power (Mains) Connection

Input Power (Mains) Connection Specifications

Voltage (U

1

)

208/220/230/240 VAC 3-phase (1-phase) +10%-15% for CPC2XXXX.

400/415/440/460/480 VAC 3-phase +10%-15% for CPC4XXXX.

Prospective Short-Circuit

Maximum allowed prospective short-circuit current in the supply is

Current (IEC 629)

65 kA in a second providing that the mains cable of the drive is

protected with appropriate fuses. US: 65,000 AIC.

Frequency

48…63 Hz

Imbalance

Max. ±3% of nominal phase to phase input voltage.

Fundamental Power

0.98 (at nominal load)

Factor (cos phi

1

)

Cable Temperature

90º C (194º F) rating minimum

Rating

Motor Connection

Motor Connection Specifications

Voltage (U

2

) 0…U

1

, 3-phase symmetrical, U

max

at the field weakening point.

Frequency

0…500 Hz

Frequency Resolution

0.01 Hz

Current

See “Ratings” on pages 131-134

Power Limit

1.5 x Rated HP

Field Weakening Point

10…60 Hz

Switching Frequency

Selectable: 1, 4 or 8 kHz

Cable Temperature

90º C (194º F) rating minimum

Rating

Frame Size

Maximum Motor Cable Length

f

sw

= 1 or 4 kHz

f

sw

= 8 kHz

Maximum Motor

R1

100 m

50 m

Cable Length

R2 - R4

200 m

100 m

R5 - R6

300 m

150 m

R7 - R8

300 m

NA

WARNING! Using a motor cable longer than specified in the chart above may cause
permanent damage to the drive or motor.

WARNING! Use of an output load filter or reactor is required when motor leads
exceed the above recommendations. Consult motor manufacturer on required use

of inverter drives.