MultiPump – Constant Pressure Control

6. Use down arrow until group parameter 1104 “MOTOR

NOM VOLTAGE” is highlighted, then press EDIT. Use the
arrows to enter your motors nameplate voltage, then press
the SAVE key.

7. Use the down arrow until group parameter 1105 “MOTOR

NOM CURRENT” is highlighted, then press EDIT. Using the
arrows, enter your motor’s maximum allowed amp draw
at full speed, or Service Factor Amps. NOTE: Enter motors
service factor from nameplate or motor manual. Once you
have entered the amps, press the SAVE key.

8. Use down arrow until you highlight group parameter 1107

“MOTOR NOM RPM”, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3550
RPM. Press the SAVE key to store setting.

9. Use down arrow until you highlight group parameter 1108

“MOTOR NOM POW”, then press the EDIT key. Use arrows to
enter the motors Horsepower rating from nameplate, then
press the SAVE key.

10.

After saving your motor horsepower, press the EXIT key. Use

the down arrow until you highlight the Group 15 “XDUCER
VARIABLES”, then press SEL.

11.

Press the down arrow until parameter 1502 “TRANSDUCER

MAX” is highlighted, then press EDIT. Default pressure
transducer setting is 300 psi. Adjust this based on your
maximum rating for a new transducer. NOTE: CentriPro
provides a 0-300 psi transducer as standard. Always check
the maximum range of your transducer before proceeding.
Select the appropriate range, then press SAVE. If no changes
are necessary, press CANCEL.

EXIT

EDIT

REM

PARAMETERS

1101 LANGUAGE

1102 APPLIC MACRO

1104 MOTOR NOM VOLT

1105 MOTOR NOM CURR

EXIT

EDIT

REM

PARAMETERS

1104 MOTOR NOM VOLT

1105 MOTOR NOM CURR

1106 MOTOR NOM FREQ

1107 MOTOR NOM RPM

3550 RPM

EXIT

EDIT

REM

PARAMETERS

1105 MOTOR NOM CURR

1106 MOTOR NOM FREQ

1107 MOTOR NOM RPM

1108 MOTOR NOM POW

1.0 HP

EXIT

EDIT

REM

PARAMETERS

1101 LANGUAGE

1102 APPLIC MACRO

1104 MOTOR NOM VOLT

1105 MOTOR NOM CURR

3.5A

EXIT

SEL

REM

PAR GROUPS

15

11 START-UP DATA

12 START/STOP

13 RAMPS/WINDOWS

14 SPD LIM/STRT LEVL

15 XDUCER VARIABLES

PROGRAMMING

EXIT

EDIT

REM

PARAMETERS

1501 TRANSDUCER UNIT

1502 TRANSDUCER MAX

300.0 PSI

1503 TRANSDUCER MIN

1504 SENSOR