Single Pump Programming (Pressure transducer)

12. From group 1402, press the down arrow until group 1502

TRANSDUCER MAX is highlighted, then press EDIT. Default
pressure transducer setting is 300 psi. Adjust this based on
your maximum rating for a new transducer. NOTE: CentriPro
provides a 0 -300 psi transducer as standard. Select the
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.

13. Use the down arrow to highlight 1503 “TRANSDUCER MIN”

0.0 , then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer value, press
SAVE to store.

14. Use the down arrow to highlight 1506 “SENSOR MIN”,

then press EDIT. Use the up arrow until the “TUNE” value is
displayed, press the SAVE key. This provides the transducer
a tune value of 0 (ZERO) psi. NOTE: Make sure that your

transducer is wired to the Aquavar but free from any

pressure in the system. The transducer must be exposed to
0 psi only when this step is performed. Press the SAVE key to
tune your transducer.

15. Final step is to enter your required pressure in

the system. After above programming has been
completed, press the EXIT key three (3) times, until
you arrive back to the first control display screen.
Then press the UP or DOWN arrow to select the
required system pressure. Once pressure has
been selected, press the green START key on the
keypad.

EXIT

EDIT

REM

PARAMETERS

1504 SENSOR

1505 K-DP FLOW METER

1506 SENSOR MIN

4 mA

CANCEL

SAVE

REM

PAR EDIT

1506 SENSOR MIN

4 mA

EXIT

EDIT

REM

PARAMETERS

1410 UNDERVOLT CTRL

1411 PRIMING DELAY

1501 TRANSDUCER UNIT

1502 TRANSDUCER MAX

300.0

EXIT

SEL

REM

15 XDUCER VARIABLES

16 REFERENCE SELECT

18 RELAY OUTPUTS

19 ANALOG OUTPUTS

21 REGULATE

PAR GROUPS

15

CANCEL

SAVE

REM

PAR EDIT

1506 SENSOR MIN

TUNED VALUE

DIR

MENU

REM

11.1%

LOC

REM

Status

LED

UP

SOFT

KEY 1

DOWN

LOC/REM

STOP

START

HELP

SOFT

KEY 2

40.2 PSI

sp

0.0 PSI

ac

0.0 HZ

PROGRAMMING