Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 56

Advertising
background image

56

Defaults
Group

Start-Up Range

Description

Single Synch- Multi- Constant Speed

11

Data

Pump ronous Control Slave Control

1104 Motor Nom

11…345V/

Defines the motor voltage.

230/ 230/ 230/ 230/ 230/

Voltage

230…690V

Equal to the value on the

460/

460/

460/

460/

460/

motor nameplate.

575 575 575 575 575

1105 Motor Nom

0.2*I

2hd

Defines the motor current.

1.0* 1.0* 1.0* 1.0* 1.0*

Current

2.0*I

2hd

Equal to the value on the

I

2hd

I

2hd

I

2hd

I

2hd

I

2hd

motor nameplate.

1106 Motor Nom Freq 10.0…500Hz Defines the motor nominal

60 60 60 60 60

frequency. Equal to the value

on the motor nameplate.

1107 Motor Nom RPM 50…18000

Defines the motor nominal

3550 3550 3550 3550 3550

RPM

speed. Equal to the value on

the motor nameplate.

1108 Motor Nominal 0.2…2.0*P

hd

Defines the motor power (hp). 1.0*P

hd

1.0*P

hd

1.0*P

hd

1.0*P

hd

1.0*P

hd

Power

Equal to the value on the

nameplate.

Group

Start/Stop Range

Description

Single Synch- Multi- Constant Speed

12

Pump ronous Control Slave Control

1201 Start/Stop

Defines the connections and

Keypad Keypad Keypad Keypad Keypad

source of the start/stop

commands.

Comment - DI1 = Enable. 0= Disable,

1 = Enable. DI2 = Low Water. 0 = Fault,

1 = OK, DI3 = Estop 0 = Estop, 1 = OK,

After Estop restart from keypad required.

Keypad

Start/Stop from keypad. After a

fault reset, the drive will restart

only if auto restart (1202) is set

to on. If auto restart is off the

drive must be started from the

keypad.

Fieldbus

Start via fieldbus control word

1202 Auto Restart

Selects whether the AV will

On On On On On

automatically restart after a

power failure or fault reset.

Off

Not selected

On

Selected. The AV will automatic-

ally restart if conditions permit.

1203 Test Run

Selects when the drive will

Not Sel Not Sel Not Sel Not Sel Not Sel

perform a test run

Not Sel (default) Not selected

PARAMETER LISTINGS

Advertising