Parameter

Name

Value/Range

Note(s)

30.01

COMM

NOT SELECTED

No fieldbus communication

PROTOCOL

(Default)

SELECT

STD MODBUS

Drive uses MODBUS protocol on the

standard RS485 port. Protocol settings

are in group 32.

EXT FBA

The drive communicates with a fieldbus

adapter module in option slot 2 of the

drive. NOTE: When EXT. FBA is selected

parameter group 31 is unlocked.

Any parameter changes that are made using a Fieldbus control system must be saved to the
drive.

Parameter

Name

Value/Range

Note(s)

10.04

PARAMETER

DONE (Default)

Parameters that are manually entered through

SAVE

SAVE

the keypad are automatically saved, only

parameters entered through a Fieldbus

connection must be saved. To save, select SAVE

and press the ENTER key.

Language
The Aquavar CPC system fully supports 3 languages; English(AM), French, and Spanish.
English(AM) refers to American English and is the default language. Units of power are in HP.

Parameter

Name

Value/Range

Note(s)

11.01

LANGUAGE

ENGLISH (AM)

ENGLISH (AM) is the default setting.

ESPANOL

FRANCAIS

Locking
The AQUAVAR CPC has three levels of control panel (keypad) locking; LOCAL LOCK,
PARAMETER LOCK and SET POINT LOCK.

PARAMETER LOCK - In parameter lock, parameters may be viewed, however they cannot

be changed. Starting, Stopping, set point changes and drive fault resets may still be
performed using the keypad. A valid password must be entered in parameter group 10.02.

LOCAL LOCK - In local lock, starting and stopping, and setpoint changes are prevented.

Resetting of drive faults is still possible and ON and OFF control.

SET POINT LOCK – When in the “ON“ position, the set-point cannot be changed from the

control panel. This prevents unwanted changes to Aquavar settings.

To change the drive parameters, including 10.03 LOCAL LOCK, the parameter lock must be
opened. To open the parameter lock, go to parameter 10.02 PASS CODE and scroll to the
number 66 and press ENTER. Parameter 10.01 PARAMETER LOCK will read OPEN.

NOTE: If power to the drive is lost [power failure, disconnect, etc…] parameter 10.01
PARAMETER LOCK will automatically reset to LOCKED.