Technical data – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 139
![background image](/manuals/310443/139/background.png)
139
Air Flow, 380…480 Volt Drives
The following table lists heat loss and air flow data for 380…480 Volt drives.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Frame
Heat Loss Air
Voltage Phase
Base
Load
DUTY
Size Flow
Model
Amps
HORSEPOWER
Watts
BTU/HR CFM
CPC40061 6.9
3
R1 97 331 26
CPC40081 8.8
5
R1 127 433 26
CPC40121 11.9
7.5
R1 172 587 26
CPC40151 15.4
10
R2 232 792 52
CPC40231 23
15
R2 337 1150 52
CPC40311 31
20
R3 457 1560 79
CPC40381 38
25
R3 562 1918 79
CPC40451 45
30
R3 667 2276 165
CPC40591 59
40
R4 907 3096 165
CPC40721 72
50
R4 1120 3820 165
CPC40771 77
60
R4 1295 4420 168
460
3 CPC40971 97
75
R4 1440 4915 168
CPC41251 125
100
R5 1940 6621 239
CPC41571 157
125
R6 2310 7884 239
CPC41801 180
150
R6 2810 9590 239
CPC42451 245
200
R7 3850 13144 319
CPC43161 316
250
R7 6850 23386 319
CPC43681 368
300
R8 6850 23386 721
CPC44141 414
350
R8 7850 26800 721
CPC44861 486
400
R8 7850 26800 721
CPC45261 526
450
R8 7600 25946 721
CPC46021 602
500
R8 8100 27653 721
CPC46451 645
550
R8 9100 31067 721
TECHNICAL DATA