Air Flow, 380…480 Volt Drives
The following table lists heat loss and air flow data for 380…480 Volt drives.

CENTRIPRO AQUAVAR CPC

NEMA 1

Full

NORMAL

Frame

Heat Loss Air

Voltage Phase

Base

Load

DUTY

Size Flow

Model

Amps

HORSEPOWER

Watts

BTU/HR CFM

CPC40061 6.9

3

R1 97 331 26

CPC40081 8.8

5

R1 127 433 26

CPC40121 11.9

7.5

R1 172 587 26

CPC40151 15.4

10

R2 232 792 52

CPC40231 23

15

R2 337 1150 52

CPC40311 31

20

R3 457 1560 79

CPC40381 38

25

R3 562 1918 79

CPC40451 45

30

R3 667 2276 165

CPC40591 59

40

R4 907 3096 165

CPC40721 72

50

R4 1120 3820 165

CPC40771 77

60

R4 1295 4420 168

460

3 CPC40971 97

75

R4 1440 4915 168

CPC41251 125

100

R5 1940 6621 239

CPC41571 157

125

R6 2310 7884 239

CPC41801 180

150

R6 2810 9590 239

CPC42451 245

200

R7 3850 13144 319

CPC43161 316

250

R7 6850 23386 319

CPC43681 368

300

R8 6850 23386 721

CPC44141 414

350

R8 7850 26800 721

CPC44861 486

400

R8 7850 26800 721

CPC45261 526

450

R8 7600 25946 721

CPC46021 602

500

R8 8100 27653 721

CPC46451 645

550

R8 9100 31067 721