Defaults
Group

Relay Range Description

Single Synch- Multi- Constant Speed

18

Outputs

Pump ronous Control Slave Control

Low Water

The secondary protection

warning or fault function has

been activated. DI4 is low for

the protection delay setting

(2404). Closed = normal,

Open = Secondary Protect fault

function is active.

Pump Protect The pump protection warning or

fault function has been activated.

Start Slave

Used in multipump macro to

start slave pump only.

Stand by

Drive is in sleep mode due to

no system demand.

1808 RO3 ON Delay

0…3600 s

Defines the operation delay for

0

0

0

0

0

relay output RO3.

1809 RO3 OFF Delay 0… 3600 s

Defines the release delay for

0

0

0

0

0

relay output RO3.

Group

Analog

Range Description

Single Synch- Multi- Constant Speed

19

Outputs

Pump ronous Control Slave Control

1901 AO 1 Content Sel

Connects a AV signal to analog Not

Not

Not

Not

Not

output 1 (AO1).

Used

Used

Used

Used

Used

Not Sel (default) Not in use.

Frequency

Output frequency. 20 mA =

motor nominal frequency (1106).

Current

Output current. 20 mA =

motor nominal current (1105).

Torque

Motor torque. 20 mA = 100%

of motor nominal rating.

Power

Motor Power. 20 mA = 100%

of motor power rating.

Proc Var/

Actual value of process variable

Actual

AI2. 20 mA = Reference 1 Max

(1603).

Energy Saving Calculated energy savings

(option 1 or 2) over a conven-

tional fixed speed system.

20 mA = Savings scale (2603).

1902 AO1 Content

Various

Selects the minimum value of the

Min

characterisitc being monitored.

1903 AO1 Content

Various

Selects the maximum value of the

4

4

4

4

4

Max

characteristic being monitored.

PARAMETER LISTINGS