Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 67

Advertising
background image

67

Defaults
Group Multipump Range

Description

Single Synch- Multi- Constant Speed

22

Control

Pump ronous Control Slave Control

2205 Sync Limit

0…60 Hz

Selects the speed at which lag

45

45

45

pump #1 (or slave #1 RO1)

should be turned off. Applies to

synchronous, multicontrol and

slave modes.

2206 Sync Window

0…60 Hz

The speed step above the sync

8

8

8

limit (2206) used to turn off lag

pump #2 (or slave #2 RO2).

Twice the Sync Window is the

speed step at which lag pump

#3 (or slave #3 RO3) is turned

off. Used for synchronous and

slave modes only.

2207 Pump Address

1…4

Defines the pump address for

1

1

1

1

1

multipump systems.

2208 Setp2 Source

OFF, 1…4

Defines which pump has the

Off

Off

Off

Off

Off

analog input connected for

second set point.

Group

Fault

Range Description

Single Synch- Multi- Constant Speed

24

Functions

Pump ronous Control Slave Control

2401 Keypad Failure

Selects how the AV will react to

a keypad communication break.

Disabled

Protection is inactive

Fault

The drive trips on fault and

the motor coasts to a stop.

A fault message is generated

“Panel Loss”.

2402 Pump Protect

Fault

Actual process value is lower

Dis-

Dis-

Dis-

Dis-

Dis-

Ctrl

than protection limit (2403) for abled abled

abled

abled

abled

protection delay (2404) and AV

is at max speed for the

protection delay.

Disabled

Protection is disabled.

(Default)

Warning

The AV generates a warning

only “Pump Protect”; no other

action is taken.

Warn and

The AV generates a warning

Control

“Pump Protect” and controls

according to the setting of

Config Speed Min (1403).

PARAMETER LISTINGS