Technical data, Ambient conditions – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 145

Advertising
background image

145

Ambient Conditions

The following table lists the AQUAVAR environmental requirements.

Ambient Environment Requirements

Installation Site

Storage and Transportation

in the protective package

• 0…1000 m (0…3,300 ft)

• 1000…2000 m (3,300…6,600 ft)

Altitude

1

if P

N

and I

2

derated 1% every

100 m above 1000 m

(300 ft above 3,300 ft).

Ambient

• -15…40º C (5…104º F)

-40…70º C (-40…158º F)

Temperature

2

• Max. 50º C (122º F) if P

N

and I

2

derated to 90%.

Relative humidity

< 95% (non-condensing)

No conductive dust allowed.

Storage

The ACS550 should be installed

• No conductive dust allowed.

in clean air according to

• Chemical gases: Class 1C2

Contamination

enclosure classification.

• Solid particles: Class 1S2

levels

• Cooling air must be clean, free

Transportation

(IEC 721-3-3)

from corrosive materials and free

• No conductive dust allowed.

from electrically conductive dust.

• Chemical gases: Class 2C2

• Chemical gases: Class 3C2

• Solid particles: Class 2S2

• Solid particles: Class 3S2

• Mechanical conditions: Class 3M4

In accordance with ISTA-1A and 1B

Sinusoidal

(IEC 60721-3-3)

specifications.

Vibration

• 2…9 Hz 3.0 mm (0.12 in)

• 9…200 Hz 10 m/s

2

(33 ft/s

2

)

Shock

Not allowed

Maximum 100 m/s

2

(330 ft/s

2

),

(IEC 68-2-29)

11ms (36 ft)

• 76 cm (30 in), frame size R1

• 61cm (24 in), frame size R2

Free Fall

3

Not allowed

• 46 cm (18 in), frame size R3

• 31 cm (12 in), frame size R4

• 25 cm (10 in), frame size R5

• 15 cm (6 in), frame size R6

(1) Consult factory above 6600’ altitude.
(2) Derate drive one HP size from motor for higher temperatures (e.g. motor HP = 10 HP; use 15 HP Aquavar in

temperature up to 122º F).

(3) R7-R8 not allowed for free fall any distance.

TECHNICAL DATA

Advertising