Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 58

Advertising
background image

58

Defaults
Group

Spd Lim/ Range

Description

Single Synch- Multi- Constant Speed

14

Strt/Lvl

Pump ronous Control Slave Control

1402 Minimum

0…Max

Defines the minimum speed

6

6

6

6

6

Frequency/Speed Frequency

range. Default setting is 10% of

parameter 1106 Motor Nom

Freq. (May want to show RPM

or HZ.)

1403 Config Speed

Defines the reaction of the drive 0

0

0

0

0

Min

when the AV tries to regulate at

a speed at or below minimum

frequency (1402).

0 (Default)

The drive will stay at Minimum

Frequency until Stp Delay Min

Spd (1404) times out; the unit

will then shutdown.

Min Freq

The AV will stay at this speed

until the transient clears or unit

is manually shutdown; unless a

fault occurs.

1404 Stp Delay

0…1800 s

The time period the drive will

0

0

0

0

0

Min Spd

stay at MinSpd (1402) before

stopping. Functions when 1403

is set to 0. Becomes active if set

point would result in regulation

below min spd, closed valve

condition in pressure control

and Secondary Protect A&B.

1405 Restart Value

0…150 %

If the drive is shutdown by

0 0 0 0 0

Config speed min (1403) due to

no system demand (pressure

control and level control only)

the drive will sleep until the

process actual value drops

below a set restart value (1405)

for longer than the restart delay

(1406). If operating in inverse

mode (2101) the drive will sleep

until the process variable rises

above the restart value. Wake-

up level in % of set point value.

To disable the Restart Value

function in both normal and

inverse settings enter “0%”.

Auto Restart (parameter 1202)

does not influence the restart

function. Default = 0.

1406 Restart Delay

0…1800 s

Time delay for restart value

0

0

0

0

0

(1405).(Default = 0 sec)

PARAMETER LISTINGS