Technical data, Cooling – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 138
![background image](/manuals/310443/138/background.png)
138
Cooling
(Frames R7-R8)
Installation Procedure
Choose the mounting orientation (a, b, c or d).
Required Free Space Around the Unit for
Frame Mounting
Mounting, Maintenance, Service and Cooling*
Size Orientation
Front
Side
Above
mm in mm in mm in
a,d
500
20
–
–
200
7.9
R7
b
–
–
500
20
200
7.9
c
–
–
200**
7.9**
lifting lifting
space space
a,d
600
24
–
–
300
12
R8
b
–
–
600
24
300
12
c
–
–
300**
12**
lifting lifting
space space
* Space for the installer not included.
** Space for the fan and capacitor replacement not included.
Mounting orientations a and b
Make holes in the wall (recommended):
1. Lift the unit against the wall into the mounting place.
2. Mark the locations for the two fixing points in the wall.
3. Mark the bottom edges of the unit to the floor.
a)
b)
c)
Lifted from above
Symbols:
required free space
air inlet surface
wall fixing point (recommended)
control panel mounting slot
TECHNICAL DATA