Technical data, Cable sizing/ratings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 131

Advertising
background image

131

Cable Sizing/Ratings

208…240 Volt Drives
The following tables provide current, horsepower, frame size and recommended cable sizes
for the Aquavar CPC.

CENTRIPRO AQUAVAR CPC

NEMA 1

Full

NORMAL

Frame

Output

Input

Voltage Phase

Base

Load

DUTY

Size

2

Cable Size

Cable Size

Model

Amps

HORSEPOWER

Min. AWG

1

Min. AWG

1

CPC20171 8.5

2

R1

14

10

CPC20241 12

3

R2

12

8

CPC20311 15.5

5

R2

12

8

CPC20461 23

7.5

R3

10

6

CPC20591 29.5

10

R3

8

4

230

1 CPC20881 44.0

15

R4

6

2

CPC21141 57.0

20

R4

4

1/0

CPC21431 71.5

25

R6

3

3/0

CPC21781 89.0

30

R6

2

4/0

CPC22211 110.5

40

R6

1/0

300MCM

CPC22481 124.0

50

R6

2/0

350MCM

CPC20121 11.8

3

R1

14

14

CPC20171 16.7

5

R1

10

10

CPC20241 24.2

7.5

R2

8

8

CPC20311 30.8

10

R2

8

8

CPC20461 46.2

15

R3

6

6

CPC20591 59.4

20

R3

4

4

230

3 CPC20751 74.8

25

R4

3

3

CPC20881 88.0

30

R4

2

2

CPC21141 114.0

40

R4

1/0

1/0

CPC21431 143.0

50

R6

3/0

3/0

CPC21781 178.0

60

R6

4/0

4/0

CPC22211 221.0

75

R6 300MCM 300MCM

CPC22481 248.0

100

R6 350MCM 350MCM

(1) Recommended AWG Size based on NEC table 310.16, 40º C ambient, 90º C, UL type copper wire. For other

wire sizes or types, consult local, state or NEC codes.

(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult

technical section (CABLE TERMINALS).