Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 71

Advertising
background image

71

Defaults
Group

Modbus Range

Description

Single Synch- Multi- Constant Speed

32

Setup

Pump ronous Control Slave Control

3201 Protocol ID

0…0xFFFF

This parameter configures the

module type automatically by

the fieldbus adapter. No action

is required by the user unless

changes to default settings are

desired. Refer to the fieldbus

manual.

3202 Station ID

0...247

1

1

1

1

1

3203 Baud Rate

1.2…57.6

9.6

9.6

9.6

9.6

9.6

kbits/s

kbits/s kbits/s kbits/s

kbits/s kbits/s

3204 Parity

Defines the data length, parity

8N2

8N2

8N2

8N2

8N2

and stop bits.

8N1

8 data bits, no parity and one

stop bit

8N2

8 data bits, no parity and two

stop bits

8E1

8 data bits, even parity and one

stop

bit.

8O1

8 data bits, odd parity and one

stop

bit.

3205 Control

Selects the communication

ABB

ABB

ABB

ABB

ABB

Profile

profile.

Drives Drives

Drives

Drives

Drives

ABB Drives

ABB Drives control word and

Status Word.

AV

Alternate Profile.

3206 OK Messages

0…65535

Read only counter of good

Modbus messages.

3207 CRC Errors

Read only counter of CRC errors.

3208 EFBUART Errors

Read only counter of UART errors.

3209 EFB Status

Contains the status of Modbus

protocol.

Idle

Drive is configured for Modbus,

but not receiving any messages.

Exec. Init

Drive is initializing Modbus.

Time Out

A time-out has occurred .

Config Error

Drive has configuration error.

Off-line

Drive is receiving messages that

are NOT addressed to itself.

On-Line

Drive is receiving messages that

are addressed to itself.

Reset

Drive is performing hardware

reset.

Listen Only

Drive is in listen only mode.

PARAMETER LISTINGS