Features – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 107

Advertising
background image

107

Pump Protect Ctrl
This feature is designed to protect the pump from lack of available NPSH, loss of or low

suction, pump run-out. This pump protection feature is exclusive to the Aquavar

®

and

measures the discharge pressure of the pump via the transducer, and compares it with the

minimum allowed system pressure as entered into parameter (2403) PROTECTION LIMIT. If

this parameter is set, then a time delay will need to be set in number of seconds allowed to

run at or below this limit, before shutting down on a fault.

Parameter

Name

Value/Range

Note(s)

24.02

PUMP

Disabled (Default)

Provides no warning, warning or

PROTECT

WARN

warning and then shut off.

CTRL

WARN & CTRL.

24.03

PROTECTION 0 – 6553.5

Actual value units.

LIMIT

24.04

PROTECTION 0 -200 seconds

Provides a time delay for 24.03.

DELAY

NOTE: It is recommended to set this pump protection according to
suggested minimum allowed system requirements. (i.e. pump run-out limits)

Regulation Mode
The regulation mode can either be NORMAL or INVERSE. The default and more common

selection is NORMAL, where the Aquavar software anticipates an increase in system pressure,

and will decrease speed of the pump based on a rising system pressure. If the regulation

mode is set to INVERSE, the process condition is expected to increase with a decrease in

pump speed.

Parameter

Name

Value/Range

Note(s)

21.01

REGULATION NORMAL (Default)

Inverse is normally used for control of

MODE

INVERSE

suction side systems.

EXAMPLE – If an Aquavar unit is trying to control the level in a suction-side tank or sump, the regulation mode

would be set to INVERSE. As the level in the sump increased, Aquavar would respond by increasing pump speed

to maintain a constant level.

Relay Outputs
The AQUAVAR CPC has three relay outputs that are configurable for different operating
and fault conditions. Relays will revert to original states once warnings or faults are reset or
cleared.
Comment(s)

Maximum Contact Voltage

30 VDC, 250 VAC

Maximum Continuous Current

2 A RMS

Refer to the terminal layout diagram for RELAY OUTPUT specifications.

Maximum Contact current/ power = 6A, 30 VDC, 1500 VA, 250 VAC

FEATURES