Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 60

Advertising
background image

60

Defaults
Group Transducer Range

Description

Single Synch- Multi- Constant Speed

15

Var

Pump ronous Control Slave Control

1503 Transducer Min 0…6553.5

For single pump and multipump

0

0

0

0

0

macros this parameter defines

the value (normally zero) of the

4 mA setting for the primary

process transmitter at AI2. This

parameter also correlates to the

minimum value of Reference

(set points) 1 and 2. For the

Speed Control macro this

parameter scales the value

(normally zero) of the 4 mA or

keypad speed setting. Note

when units are in Ft, M, In or

Cm: AI2 Min is always based on

a specific gravity = 1 regardless

of setting for parameter 1506.

Actual pressure signals in Ft, M,

In or Cm are corrected for

specific gravity by the firmware.

Signal can be quadratic or linear.

1506 Sensor Min

Defines the value for analog

4 mA

4 mA

4 mA

4 mA

4 mA

(

Not in Software)

sensor input.

4 mA (Default) 4 mA is selected as the

minimum value.

Tuned Value

Select tuned value after the tune

function has been completed.

This will select the tuned value

for the minimum value of

sensor input.

Tune

This parameter sets the mini-

mum value of the signal to be

applied to sensor input. When

tune is selected and enter is

pressed the tuned value for

sensor input is set to the actual

sensor input value when the

tune function was activated.

This function is useful for zeroing

out any system hysteresis.

PARAMETER LISTINGS