Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 62

Advertising
background image

62

Defaults
Group

Reference Range

Description

Single Synch- Multi- Constant Speed

16

Select

Pump ronous Control Slave Control

1604 AI 1 Minimum

Tune

This parameter sets the minimum 4-20

4-20

4-20

4-20

4-20

(continued)

value of the signal to be applied mA

mA

mA

mA

mA

to AI1. When tune is selected

and enter is pressed the tuned

value for AI1 is set to the actual

AI1 value when the tune

function was activated. This

function is useful for zeroing

out any system hysteresis.

Group

Relay

Range Description

Single Synch- Multi- Constant Speed

18

Outputs

Pump ronous Control Slave Control

1801 Relay RO1

Selects the AV status to be

Ready Ready

Ready

Start

Ready

Output

indicated through relay output 1

Slave

(RO1). The relay energizes when

the status meets the setting.

Relay warnings are reset

automatically, faults must be

manually reset.

Not Sel

The output is not used

Run

The output indicates the drive is

running.

Ready (Default) The output indicates that power

is supplied to the drive and it is

awaiting a start command.

VFD Fault

The drive has faulted

Low Water

The secondary protection

warning or fault function has

been activated. DI4 is low for

the protection delay setting

(2404). Closed = normal,

Open = Secondary Protect fault

function is active.

Pump Protect The pump protection warning or

fault function has been activated.

Start Slave

Used in multipump macro to

start slave pump only.

Stand by

Drive is in sleep mode due to no

system demand.

1802 RO1 ON Delay

0...3600 s

Defines the operation delay for

0

0

0

0

0

relay output RO1.

1803 RO1 OFF Delay 0…3600 s

Defines the release delay for

0

0

0

0

0

relay output RO1.

PARAMETER LISTINGS