Logbook messages: "slave at index x missing" with, Cyclic command wkc error, Cyclic command wkc error ..." ( 154) – Lenze EtherCAT control technology User Manual

Page 154: Control technology | ethercat communication manual

Advertising
background image

Control technology | EtherCAT communication manual

Diagnostics

Error scenarios

154

L

DMS 3.1 EN 01/2011 TD17

11.6.11

Logbook messages: "Slave at index X missing" with "Cyclic command WKC error ..."

The "Cyclic command WKC error" message is entered cyclically every 5 seconds into the

logbook of the industrial PC until the error is not active anymore.

...

xxxxx DD-MM-YYYY hh:mm:ss
EtherCAT Master Stack

SLV: Cyclic command WKC error on LWR - Address: 0x10000 -
WKC act/set=2/7
Communication on bus systems
Error

...

xxxxx DD-MM-YYYY hh:mm:ss
EtherCAT Master Stack

SLV: Slave at index X missing. State req/act=Operational/
UNKNOWN
Communication on bus systems
Error

...

Causes

Remedies

The bus cable between two EtherCAT nodes has been

unplugged.

1.Stopping the PLC program: Execute the menu

command OnlineStop.

2.Plug in the bus cable.

3.Execute the SMC_ResetAxisGroup function block or a

Bus restart ( 139)

.

(For this, see also

Logbook message: "Cyclic command

WKC error ..." ( 156)

.)

The node at position X is deenergised.

Switch-on the node and execute the

SMC_ResetAxisGroup function block or a

Bus restart

( 139)

.

Advertising