Lenze EtherCAT control technology User Manual

Page 95

Advertising
background image

DMS 3.1 EN 01/2011 TD17

L

95

Control technology | EtherCAT communication manual

EtherCAT with CANopen or PROFIBUS

Addressing EtherCAT nodes using CANopen/PROFIBUS nodes

In the »PLC Designer«, the output and input objects are "byte-addressed". The original

address offset of ’1000’ (word level) for the first output and input objects is set accordingly

to '2000" after the import of the EtherCAT configuration. The addresses of the other input

and output objects are also updated.

Note!

• Changes of the EtherCAT configuration in the »PLC Designer« are overwritten

when the EtherCAT configuration is re-imported.

Always adapt the EtherCAT configuration to the »EtherCAT Configurator«.

• In a mixed operation, it must always be ensured that the CAN-Motion task

has the highest priority. The task assigned to the EtherCAT bus should have

the second-highest priority. The tasks assigned to the Logic bus systems

should be configured with a lower priority.

Advertising