Control technology | EtherCAT communication manual

EtherCAT function libraries

Properties of function blocks

98

L

DMS 3.1 EN 01/2011 TD17

9.3

Properties of function blocks

The function blocks are equipped with inputs and outputs for the activation of the POU,

the display of the current POU status, and for the output of error messages:

9.4

The EC_T_STATE structure

The ECAT_STATE structure describes all possible states of the EtherCAT bus system:

Input/output

Data type

Action

bExecute / bEnable

BOOL

bExecute and bEnable are edge-controlled:

In the case of a positive edge, the function block is executed.

bBusy

BOOL

As long as a function block is executed, bBusy is TRUE and bDone is FALSE.

bDone

BOOL

If a function block has been executed, bDone is set to TRUE and bBusy is set

to FALSE.

If bExecute/bEnable has been reset, bDone is only active during the function

block call. If bExecute/bEnable is TRUE, then bDone remains TRUE as long as

bExecute/bEnable is reset.

bError

BOOL

If an error has occurred, bError is set to TRUE.

dwErrorCode

DWORD

If an error has occurred (output bError = TRUE), a hexadecimal error code (see

also

System error messages ( 157)

) is displayed at the output dwErrorCode.

The error code is only available during the function block call (if

bDone = TRUE).

Note!

The identifiers itemised here cannot be found in IEC 61131. For all state inputs

and outputs, always the numerical values are indicated.

Status

Identifier

Value (DINT)

Unknown

eEcatState_UNKNOWN

0

Initialization

eEcatState_INIT

1

Pre-Operational

eEcatState_PREOP

2

Bootstrap Mode

(Is currently not supported.)

eEcatState_BOOT

3

Safe-Operational

eEcatState_SAFEOP

4

Operational

eEcatState_OP

8