Control technology | EtherCAT communication manual

Commissioning of the system

Checking the system startup

7.3.2

Evaluation of the Axis_IO_Group state

The Axis_IO_Group structure contains the global variable wState.
The following value ranges have to be evaluated for the system startup check:

The value of the wState variable has the following meaning:

State of the Axis_IO_Group

State of the system

wState = 0

• Initial state

• Project loaded

• PLC in stop

wState = 1...99

• System is starting up

• Project loaded

• PLC started

wState = 100

• System has started up successfully

wState > 1000

• Error occurred during startup, compare error message in

g_strBootupError